G 28.0 N Bi-directional in-line detonation flame arrester, short-time burning proof

KITO® RG-Det4-IIC-…
KITO® RG-Det4-IIC-…-T (-TT)
-design with flange connection –

  • For installation into pipes to the protection of vessels and components against stable detonation of flammable liquids and gases.
  • Tested and approved as detonation flame arrester type 4.
  • Approved for all substances of explosion groups IIA1 to IIC with a maximum experimental safe gap (MESG) < 0.5 mm.
  • Bi-directionally working in pipes, whereby an operating pressure of 1.2 or 1.1 bar abs. and an operating temperature of 60 °C must not be exceeded.
  • All sizes are tested against “stabilized burning” and withstand this up to a max. burn time BT ≤ 1.0 min.
  • To detect a “stabilized burning” a temperature sensor must be installed at each endangered side.
  • Mounting is acceptable in any position, in horizontal as well as in vertical pipes.
Download